Description
| Country of origin | Romania |
| Nominal voltage U0 | 12 kV |
| Nominal voltage U | 20 kV |
| Maximum operating voltage Umax | 24 kV |
| Rated current earth | 285 A |
| Rated current air | 323 A |
| Conductor resistance | 0.253 Ω / km |
| Conductor cross-section S | 120 mm² |
| Conductor shield cross-section | 16 mm² |
| Conductor diameter S | 30.7 mm |
| Bending radius | 461 mm |
| Conductor class | 2 |
| Number of cores | 1 |
| Type | NA2XSY 12/20 kV |
| Type | 1 x 120 RM / 16 |
| Core type | RM |
| Core form | Round |
| Core form | Stranded |
| Core insulation | XLPE |
| Inner semi-conducting layer | X |
| Outer semi-conducting layer | X |
| Conductive wrapping | X |
| Screen braiding of copper wires with counter helix conductors | X |
| Wrapping | X |
| Flame retardant | X |
| Indoor use | X |
| Outdoor use | X |
| Core material | Aluminium |
| Outer sheath material | Polyvinyl chloride PVC |
| Outer sheath colour | Red |
| Temperature | -20 …+70 °C |
| Maximum conductor temperature | 90 °C |
| Weight | 1036 kg / km |
| Standard | HD 620 S2 |
| Standard | IEC 60228 |
| Standard | IEC 60502 |