Description
| Country of origin | Ukraine |
| Dry lightning impulse withstand voltage | 140 kV |
| Dry power-frequency withstand voltage | 90 kV |
| Wet power-frequency withstand voltage | 55 kV |
| Puncture voltage in oil | 130 kV |
| Rated frequency | 50 … 60 Hz |
| Specified mechanical load | 210 kN |
| Creepage distance | 555 mm |
| Spacing A | 170 mm |
| Standard coupling B | 20 mm |
| Insulating diameter C | 330 mm |
| Type | Anti-pollution |
| Class | U210BP |
| Material | Glass |
| Temperature | -40 …+50 °C |
| Standard | IEC 60120 |
| Standard | IEC 60305 |