Description
| Country of origin | Germany |
| Rated short circuit current | 29.6 kA |
| Rated time | 0.5 s |
| Total length L | 5190 mm |
| Transport length T | 2870 mm |
| Handle length H | 1900 mm |
| Insulating length I | 3290 mm |
| Diameter D | 26 mm |
| Diameter D | 43 mm |
| Mechanical load | 8 kg |
| Type | Earthing |
| Telescopic | X |
| Indoor use | X |
| Outdoor use | X |
| Material | Glass-fibre reinforced polyester |
| Temperature | -25 …+55 °C |
| Standard | DIN 48087 |
| Standard | DIN VDE 0683-100 |
| Standard | EN/IEC 61230 |